Features

Technical Parameters

1.Special air conditioning and U-shape air duct design

• Adopt rack air conditioning + outdoor unit scheme to guarantee the minimum failure rate of and convenient maintenance of indoor unit. When the indoor unit breaks down, it shall guarantee that IT equipment operation will not be affected..

2.Sealed cabinet, emergency ventilation design

• RDC cabinet is the closed assembled cabinet. The internal IT equipment space is designed as per standard 19in specification, and both front and back doors adopt tempered glasses. 32-36U IT equipment installation space can be provided except the supporting facilities inside the cabinet.

• The emergency ventilation can be realized when the air conditioning breaks down. The cabinet is standard equipped with anti-static wristlet to reduce the risks of static electricity to IT equipments.

 

3.Power supply, standby and distribution system, Li-battery UPS

• The cabinet is equipped with power supply equipments such as input air switch, Li-UPS and PDU, which is designed as per 10A load for single cabinet, i.e. 2200W.

• UPS load capacity is 3KVA, and the backup mode or online mode can be selected. It adopts LI-FE battery as its backup battery, realizes the advantages of lighter, smaller and safer than lead-acid battery, and no harmful impact on IT equipments, and realizes over 30 min full-load standby power supply; the anti-thunder module is optional according to the power using condition of the unit room.

  

4. Monitoring system, system-wide remote monitoring and management

• The cabinet is equipped with host monitoring computer. The parameters of air conditioning (including environment temperature and humidity), UPS (including power supply) are monitored by serial port communication. The access control, smoke detector and water immersion sensors are deployed, and security video monitoring interface shall be reserved.

 

5. More functions are optional

• Huawei four-node server, storage: guarantee to realize maximum computation and storage resource configuration in listed space and power capacity;

  • IP PBX or voice gateway device, router and interchanger: can realize telephone and website communication of the unit;

 • HFA fire trace tube full-automatic fire extinguishing system: realizes automatic booster and submerged fire extinguishment;

 • Anti-thunder module: install second grade anti-thunder module in UPS input terminal, and standard equip third grade anti-thunder in PDU. Realize protection of IT load by third grade anti-thunder module.

Wish you can find your favorite best UK replica watches on this website with less money.

All the hot UK cheap fake watches with Swiss movements are available.

 

Type

Item

Specification

 

Cabinet

Model

Sealed assembled cabinet, tempered glass door

Size

650×980×2040mm

Capacity

32-36U

Weight

About 180kg

 

Air conditioning

Model

Precision industrial air conditioning

Size

Standard 19in, 4U

Refrigerating capacity

2600W

EER

3.0

Outdoor unit power

1000W

 

 

 

Power supply

Model

Li-UPS

Size

Standard 19in, 4U

Working mode

Backup or online

Loaded power

3000VA

Output power factor

0.8

Efficiency

Backup 98%, online 88%

Battery type

Lithium Iron Phosphate

Battery capacity

1500WH

Power distribution

Input air switch, output PDU

 

 

 

 

 

 

Monitoring

Monitoring parameter

Voltage, battery capacity, load current, temperature, humidity, access control, smoke detector and water immersion

Display parameter

Temperature, humidity

Monitoring interface

RS485/RS232

Network interface

RJ45

Sensor quantity

Maximum 12

Size

Standard 19in, 1U

Remote monitoring

Active client query, inform warming by client or telephone

Control function

Emergency ventilation open and close, load cutoff and recovery