Features
Technical Parameters
1.Special air conditioning and U-shape air duct design
• Adopt rack air conditioning + outdoor unit scheme to guarantee the minimum failure rate of and convenient maintenance of indoor unit. When the indoor unit breaks down, it shall guarantee that IT equipment operation will not be affected..
2.Sealed cabinet, emergency ventilation design
• RDC cabinet is the closed assembled cabinet. The internal IT equipment space is designed as per standard 19in specification, and both front and back doors adopt tempered glasses. 32-36U IT equipment installation space can be provided except the supporting facilities inside the cabinet.
• The emergency ventilation can be realized when the air conditioning breaks down. The cabinet is standard equipped with anti-static wristlet to reduce the risks of static electricity to IT equipments.
3.Power supply, standby and distribution system, Li-battery UPS
• The cabinet is equipped with power supply equipments such as input air switch, Li-UPS and PDU, which is designed as per 10A load for single cabinet, i.e. 2200W.
• UPS load capacity is 3KVA, and the backup mode or online mode can be selected. It adopts LI-FE battery as its backup battery, realizes the advantages of lighter, smaller and safer than lead-acid battery, and no harmful impact on IT equipments, and realizes over 30 min full-load standby power supply; the anti-thunder module is optional according to the power using condition of the unit room.
4. Monitoring system, system-wide remote monitoring and management
• The cabinet is equipped with host monitoring computer. The parameters of air conditioning (including environment temperature and humidity), UPS (including power supply) are monitored by serial port communication. The access control, smoke detector and water immersion sensors are deployed, and security video monitoring interface shall be reserved.
5. More functions are optional
• Huawei four-node server, storage: guarantee to realize maximum computation and storage resource configuration in listed space and power capacity;
• IP PBX or voice gateway device, router and interchanger: can realize telephone and website communication of the unit;
• HFA fire trace tube full-automatic fire extinguishing system: realizes automatic booster and submerged fire extinguishment;
• Anti-thunder module: install second grade anti-thunder module in UPS input terminal, and standard equip third grade anti-thunder in PDU. Realize protection of IT load by third grade anti-thunder module.
Wish you can find your favorite best UK replica watches on this website with less money.
All the hot UK cheap fake watches with Swiss movements are available.
Type |
Item |
Specification |
Cabinet |
Model |
Sealed assembled cabinet, tempered glass door |
Size |
650×980×2040mm |
|
Capacity |
32-36U |
|
Weight |
About 180kg |
|
Air conditioning |
Model |
Precision industrial air conditioning |
Size |
Standard 19in, 4U |
|
Refrigerating capacity |
2600W |
|
EER |
3.0 |
|
Outdoor unit power |
1000W |
|
Power supply |
Model |
Li-UPS |
Size |
Standard 19in, 4U |
|
Working mode |
Backup or online |
|
Loaded power |
3000VA |
|
Output power factor |
0.8 |
|
Efficiency |
Backup 98%, online 88% |
|
Battery type |
Lithium Iron Phosphate |
|
Battery capacity |
1500WH |
|
Power distribution |
Input air switch, output PDU |
|
Monitoring |
Monitoring parameter |
Voltage, battery capacity, load current, temperature, humidity, access control, smoke detector and water immersion |
Display parameter |
Temperature, humidity |
|
Monitoring interface |
RS485/RS232 |
|
Network interface |
RJ45 |
|
Sensor quantity |
Maximum 12 |
|
Size |
Standard 19in, 1U |
|
Remote monitoring |
Active client query, inform warming by client or telephone |
|
Control function |
Emergency ventilation open and close, load cutoff and recovery |