Features
Technical Parameters
1.Online/backup mode optional
UPS works in ECO mode normally, and will automatically convert to AC inversion mode or battery inversion mode when output voltage is higher than set range or AC is off to guarantee the load will be supplied with uninterruptable power.
Let me introduce you replica watches uk which brands are today. The popularity is good.
You can find 1:1 best rolex replica watches UK on this website. Direct online order, convenient and efficient.
You can buy forever UK fake watches for sale online.
2.Batch charging will improve the service life of battery
Solve the influence of floating charge on the service life of battery
3.Comprehensive battery protection improves the safety of the system
Battery cell protection – pressure release value/membrane design for battery cell;
Battery group protection – adopt BMU to guarantee the Li-battery operates stably and reliably
System protection – automatic battery inspection and discover faults and warm in time.
4.Excellent performance of Li-FE battery
High energy density – small size, light weight, supportive for wall installation
Good high and low temperature resistance performance- Li-battery can realize high-capacity discharging within -20 - +70℃ with good temperature performance
Super-long service life – circular service life is longer than 1000 times;
High-rate discharge performance – small capacity can solve large problems and the application is more flexible;
Safety – by strict short circuit tests and destructive test, it does not catch fire or explode;
Environmental protection – heavy-metal-free, non-toxic, pollution-free.
Buying is earning! You cannot miss the online shop of UK AAA replica watches with high quality.
Men and women are both worth the luxury rolex replica watches UK.
Set Module: |
HT1000E |
HT2000E |
HT3000E |
System capacity |
1KVA/0.8KW |
2KVA/1.6KW |
3KVA/2.4KW |
System efficiency |
ECO Mode: ≥98%/Inversion mode:≥88% |
||
Input features |
|||
Rated input voltage |
220VAC(single-phase three wire system) |
||
Rated of input voltage |
(120~288)VAC |
||
Range of input frequency |
(48~52)HZ |
||
Input power factor |
≥0.97(full load) |
||
Output features |
|||
Output voltage |
ECOoutput:200-240VAC,nversion output 220(±1%)VAC |
||
Output power factor |
0.8 |
||
Output wave |
Sine wave |
||
Output frequency |
ECO Output:(48~52)HZ |
||
AC inversion:(48~52)HZ |
|||
Battery inversion:(49.9~50.1)HZ |
|||
Current peak value ratio |
3:1(Max.) |
||
Wave distortion degree |
Linear load, when in full load THD≤3% |
||
Non-linear load, when in full load THD≤5% |
|||
Conversion time |
Bypass mode → Battery mode, Bypass – inversion switching time <10ms |
||
Battery mode →Bypass mode: <2ms |
|||
Overload capacity |
Inverter: under AC inversion mode: when under 105%~125% rated load for 1min, the system will mark alarm and turn to bypass output; when the overload is eliminated, UPS can automatically turn back to inversion mode |
||
ECO Mode: Make alarm under 95%-120% load, and turn to standby mode when the load is 120% larger (cut off the output); the status can be inquired by RS232 |
|||
Complete set efficiency |
Inversion output: ≥88% (Full load) |
||
ECO Mode: ≥98% (Full load or full battery) |
|||
Output short-circuit protection |
AC/Battery inversion: cut off inversion output and make alarm |
||
ECO Mode: Over-current self-recovered safety +FUSE (fast fuse) |
|||
Internal protection |
In case of internal failure of UPS (such as inversion/BUS motor, generator overheat), turn off the inverter, DC/DC boot and PFC boot circuits, turn to bypass output and display alarms. |
||
Battery |
|||
Circular service life |
More than 1000 times |
||
Working temperature |
-20℃~60℃ |
||
Working condition |
|||
Noise |
≤45dBA (1m right ahead of panel) |
||
Working temperature |
-20℃~60℃ |
||
Altitude |
The altitude shall be less than 1000m. When it is higher than 1500m, the set shall be used by reducing rated power. |
||
Appearances |
|||
Net weight |
9Kg Excluding storage battery |
||
Size (mm)W×D×H |
440*400*88(2U) |
||
Input socket |
1 Piece |
||
Output socket |
National standard ×2(10A) |